Hello
I am connecting a diesel generator which is a new replacement for an existing generator.
First, I installed a new breaker panel - the old one was shot - with the appropriately sized double-pole breaker (the generator is 120/240 volts AC hence needs a 2-pole breaker).
This breaker panel protects the wiring between itself and the main boat panel when the master switch is set to “generator” (instead of “shore”). It also protects against overload, that is, if the total loads running off the generator exceed the breaker rating, it will blow.
The breaker’s amp rating is less than that of the wires it’s protecting and, also, just a little higher than the generator’s rating (so it won’t blow for momentary surges such as motor startups). So, it functions essentially the way a main house breaker does (the main service panel located right after the meter in a house).
My question is this: the ABYC (and other, I think) standards state that the maximum length of wire from a generator to its breakers must not exceed 7″ or 40″ if the wires are encased. Because of physical limitations, I needed to place the breaker panel about 6′ away (length of the wires) from the generator. So, do I need to provide additional protective devices closer to the generator to protect the AC output wires between the generator and the “service panel”?
I was thinking of putting a set of fuses, rated higher than the service breaker but less than the wires’ rating, right at the generator. I could do this because the fuses would take up less space than the breaker panel. Should I do this ? My impression is that regardless of the rules, this is not often done even when the distance exceeds the 40″.
To explain further, the sole purpose of these fuses would be to protect the relatively short run (6′) of wire from the generator to the breaker panel.
In the case of an overload/short, etc in a device running from generator power, for example an air conditioner, the breaker on the boat’s main panel for the specific device’s circuit should blow first, as normal. In the case of a cumulative load where no individual circuit is overloaded but the total load exceeds the generator’s capacity, the breaker in the panel I installed would blow. This would also occur if there were a short in the wire runs between the boat main panel and the generator panel I installed. If there were a short in the wires between the generator and the breaker I installed, the fuse(s) would blow.
This is really a similar situation where in many boats, at least older ones, with 12 V d.c. systems. There is no fuse/breaker at the battery, There is often a fairly long run of wire from the hosue battery to the boat’s main panel, and, should there be a short, etc. in that wire, there would be no protection.
Thank you
Ken
Ken,
If your generator does not have output breakers on it, it is probably self limiting.
Per the exception on ABYC E-11.7.3: “Self limiting generators, whose maximum overload current does not exceed 120 percent of its rated current output, do not require additional external overcurrent protection.”
Check into this before you start adding un-necessary breakers.
Kevin